Commissioning the AS-Interface safety monitor
5.4 Teach safe configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
142 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
If not all of the safe AS-Interface slaves which are to be monitored can be set to the switched-
on state (ON) simultaneously, the following window appears in which the progress of the tea-
ching process is graphically depicted.
Now, one after the other, set all safe AS-Interface slaves whose code sequences could not
previously be read to the switched-on state (ON) for several seconds. The configuration is con-
tinuously read by the AS-Interface safety monitor. The display of the safe AS-Interface slaves
which have already been taught and those which still need to be taught is updated constantly.
As an alternative to this, you can also manually enter the code sequence of a safe AS-Interface
slave. To do this, double-click the checkbox of the respective safe AS-Interface slave in the CT
column (code table). The following window for manual input of the code sequence opens.
Enter the correct code sequence and confirm your entry with OK.
Upon successful conclusion of the teaching process or after entering all code sequences, click
OK. Immediately afterward, the preliminary configuration log is transmitted to ASIMON.
Note
In the Incremental teach window, switch states S1 and S2 are displayed for the respective
slaves in addition to the teach state. In this way, you can also detect possible device malfunc-
tions or communication faults from a single screen.
Incremental teaching of the code sequences also functions with older AS-Interface safety mo-
nitor models, but takes longer as the entire configuration must always be loaded into the safety
monitor between two successive teach operations.