DNP Options Module Settings
The DNP Options module provides global settings that affect all DNP Slave
Export and DNP Slave Import modules. The default settings in this module
are shown in the following table.
Setup Register Setting Function
BinInStatic Single-bit Binary Input variant for Binary Input Static objects
BinInEvents Binary Input Change w/o
time
variant for Binary Input Event objects
BinInEvDepth 100 maximum number of Binary Input Events that can be stored
BinCntStatic 16-bit Binary Counter w/o
flag
variant for Binary Counter Static objects
FrzCntStatic 16-bit Frozen Counter w/o
flag
variant for Frozen Counter Static objects
FrzCntEvents 16-bit Frozen Counter Event
w/o time
variant for Frozen Counter Event objects
FrzCntEvDepth 100 maximum number of Frozen Counter Events that can be stored
CntChangeEvents 16-bit Counter Change Event
w/o time
variant for Counter Change Event objects
CntChangeEvDepth 100 maximum number of Counter Change Events that can be stored
AIStatic 16-bit Analog Input w/o flag variant for Analog Input Static objects
FrzAIStatic 16-bit Frozen Analog Input
w/o flag
variant returned from Class 0 poll for Frozen Analog Input Static
objects
FrzAIEvents 16-bit Frozen Analog Event
w/o time
variant for Frozen Analog Input Event objects
FrzAIEvDepth 100 maximum number of Frozen Analog Input Events that can be stored
AIChangeEvents 16-bit Analog Input Change
Event w/o time
variant for Analog Input Change Event objects
AIChangeEvDepth 200 maximum number of Analog Input Change Events that can be
stored
AOStatic 16-bit Analog Output Status variant for Analog Output Block objects
SelectTimeout 10 Select Before Operate timeout period (in seconds)
TimeSynchPeriod 86400 time (in seconds) between IED requests for time syncs
ALFragSize 2048 maximum application layer message size (in octets) that IED can
send
DLAck Never when device will request data link layer acknowledgements
DLTimeout 2 how long data link layer waits for acknowledgement from Master
DLNumRetries 0 how many times a data link layer packet is re-sent after failing