I/O Module Installation and Wiring - I/O Installation Procedures
Revision 5 HC900 Hybrid Controller Installation and User Guide 67
9/03
Step Procedure Comments Reference
7
Connect wire shield to
grounding bars on top
and/or bottom of the Rack.
(Refer to Signal
Grounding, at the
beginning of this section,
for suggestions and
recommendations.)
8
Install I/O modules in
racks.
9
In each slot location not
occupied by an I/O
module, install a Filler
Block cover, Part number
900TNF-0001.
Note: The Filler Block Cover looks much like an I/O Terminal
Block assembly, except that it does not include the wire
terminating block (screw terminals). The Filler Block mounts in
the same manner as a Terminal Block (with captured screws at
top and bottom). Blank labels are provided for mounting in the
hinged door.