Pre-Installation Planning - Environment
38 HC900 Hybrid Controller Installation and User Guide Revision 5
9/03
Environment
Environmental Operating Limits
The environmental conditions required for operating the HC900 Hybrid Controller are listed Table 6.
Table 6 - Operating Limits and Installation Guidelines
Condition Specifications
Ambient Temperature
32°F to 131°F (0°C to 55°C) or (0°C to 60°C) with derating
Relative Humidity 10 % to 90 % RH at 40°C (104°F)
Vibration
Frequency
Acceleration
14 Hz to 250 Hz
1 g
Mechanical Shock
Acceleration
Duration
1 g
30 ms
Electromagnetic Interference (EMI) and
Radio Frequency Interference (RFI)
Meets the requirements of the EMC directive, 89/336/EEC.
Evaluated to EN61326:1997 + A1 for emissions and
immunity.
Power
Voltage
Frequency (Hz)
100 Vac to 240 Vac
47 to 63 Hz
Power Consumption Typical 110VA@ 115VAC, maximum 130VA @ 264VAC
Class 1, Division 2 Installations
CONTROLLER RACK MUST BE MOUNTED INSIDE A
SECURE ENCLOSURE
General Installation Install per NEC requirements for Open Type Equipment